Counter Down
Introduction
The down-counter can be used to signal when a count has reached zero after counting down from a preset value PV
.
The counter CV
is initialized to PV
when the load command LD
is TRUE
.
If the input CD
has a rising edge FALSE
to TRUE
transition, CV
is decremented by 1, provided that CV
is greater than 0.
The output Q
is set to TRUE
when CV
is less than or equal to 0.